  • CL6880MA integrated system integrated monitoring module

    CL6880MA is a product developed for the application of power integration system, which integrates the related detection and control functions of the AC and DC buses of the charging cabinet. It can be used as the overall monitoring of the integrated system with one charge and one battery, and can also be used as a sub-monitor of a large system with two batteries and two batteries or three batteries and two batteries.

I. System overview
      CL6880MA is a product developed for the application of power integration system, which integrates the related detection and control functions of the AC and DC bus of the charging cabinet. It can be used as the overall monitoring of the integrated system with one charge and one battery, and can also be used as a sub-monitor of a large system with two batteries and two batteries or three batteries and two batteries.
      
CL6880MA adopts integrated design, which simplifies system design to the greatest extent. Compared with the configuration screen monitoring system, CL6880MA×1=7inch configuration screen monitor×1+24VAuxiliary power×1+DB9Signal Adapter×1+RS232/RS485Protocol Converter×1+< /span>AC/DC integrated detection unit×1+IRIG-BTimer×1+Hall current sensor×2.
In addition,CL6880MAThe monitoring system adopts modular The design idea, combined with modular power distribution monitoring products, can flexibly meet diverse design requirements.
Second, product features

Ø  7-inch touch screen, graphical display, system configuration parameter setting, status, data and alarm record query, etc.;

Ø  220V/110V bus voltage direct power supply;

Ø  Collection2 Single-phase/ Three-phase AC voltage, try with or without AC neutral;2AC incoming line switch mutual throw and interlock control;

Ø  Collect bus voltage, control bus voltage, battery voltage, battery current, load current, 8Road low pressureDIinput.
A, battery< span style="font-size:16px;line-height:1.5;">/Load current acquisition can be directly from the shunt acquisition without Hall current sensor;

B, 8-way low voltageDI span>Input can detect special switch values such as battery fuse alarm, air circuit breaker tripping; customizable; span>

Ø  It has the function of insulation detection host, which can detect positive and negative busbar-to-ground resistance and AC break-in voltage; this function can be turned off;

Ø  3 points7level silicon chain automatic control function, this function can also be turned off to achieve3Dry contact output; customizable;

Ø  7-way alarm dry contact output; can be customized;

Ø  1 channel sound and light alarm output;

Ø  WithIRIG-B Time synchronization function (GPShard pair);

Ø  With battery intelligent management function, battery offline detection, support battery management of lead-acid battery or nickel-cadmium battery;

Ø SupportU Disk import, export data and configuration files, program upgrade;

Ø  Support Chinese and English display interface;

Ø supportModbus ,CDT91, IEC61850(optional) communicate with background;

Ø Support and charging module, communication power module,UPS/Inverter communication and management.

Ø  Extended functionality:
A, Optional switch detection module 6881M01, can realize AC screen, DC screen, communication power screen, UPS/Inverter screen and other input and feed-out branch status/Alarm point detection, up to 56*16Road Switch detection;
B, optional Digital leakage current sensorSLD1S-10mA/SLDS1K-10mA (with 2channel switch value), can achieve32Insulation inspection and switch value inspection of feeder branches of 1 and below;
C, optional Insulation detection module 6889M01 (host)+ 6889M01C (slave), can realize bus insulation inspection, AC break-in and feed-out branch insulation inspection, the maximum can be achieved 32*16Insulation inspection of feeder and branch circuits.
D. Optional Battery inspection instrument 6882M01(24section ) or  6882M02( 54 section), which can detect the voltage of a single cell of the battery pack and the ambient temperature of the battery pack;
E, optional AC acquisition moduleAC88-3-V2, can realize the three-phase voltage and current collection of AC screen incoming line or bus.